Medium frequency induction melting features fast heating speed, high efficiency, low burning loss, small melting loss and low heat loss. It brings relatively low workshop temperature, reduces smoke and dust generation, and has remarkable effects in energy conservation, productivity improvement, labor condition improvement, labor intensity reduction and workshop environment purification. Especially for cast iron, induction melting furnaces are conducive to obtaining low-sulfur molten iron, which is incomparable to cupolas. When casting enterprises select medium frequency melting furnaces, they should take transformer capacity, output requirements, investment quota and other factors as selection criteria, and pay attention to the following precautions when purchasing equipment.
1. Electricity Requirements for Medium Frequency Induction Melting
1.1 Transformer Capacity for Medium Frequency Induction Melting
For the currently commonly used SCR full-bridge parallel inverter medium frequency power supply in the industry, the relationship between transformer capacity and power supply power is: Transformer capacity = Power supply power × 1.2. For IGBT half-bridge series inverter medium frequency power supply (commonly known as one-drive-two configuration, one unit for melting and one for heat preservation, both work simultaneously), the relationship between transformer capacity and power supply power is: Transformer capacity = Power supply power × 1.1. To reduce harmonic interference, the rectifier transformer should be dedicated to single equipment as far as possible, that is, one medium frequency power supply is equipped with one rectifier transformer.
1.2 Incoming Line Voltage for Medium Frequency Induction Melting
Medium frequency power supplies below 1000KW generally adopt 380V, 50HZ industrial electricity with three-phase five-wire system, and are equipped with 6-pulse single rectifier medium frequency power supply. For medium frequency power supplies above 1000KW, 660V incoming line voltage is preferred (some manufacturers use 575V or 750V. Since 575V or 750V are non-standard voltage levels, accessories are difficult to purchase, so it is not recommended to choose them), and 12-pulse double rectifier medium frequency power supply is configured. There are two reasons: first, increasing the incoming line voltage can raise the rated working voltage; second, harmonics generated by high power will interfere with the power grid. Double rectification can obtain relatively stable DC current, the load current is a rectangular wave, and the load voltage is close to a sine wave, which reduces the impact of power grid interference on other equipment. Some users blindly pursue high voltage (some 1000KW equipment use 900V incoming line voltage) and low current to achieve the purpose of energy saving, but they do not know that this is at the cost of the service life of the electric furnace, which is not worth the loss. High voltage is easy to shorten the service life of electrical components, cause fatigue of copper bars and cables, and greatly reduce the service life of the electric furnace. In addition, for electric furnace manufacturers, high voltage reduces raw material consumption and saves costs, so they are definitely willing to do this (high selling price with low cost), and ultimately it is the equipment user that suffers losses.
2. Output Requirements
Generally speaking, the capacity of a medium frequency induction melting furnace can be determined according to the weight of single tapping and the total required molten iron weight per working day, and then the power and frequency of the medium frequency power supply are determined. Induction heating equipment is a non-standard product, and there is no unified national standard for it at present. The common configuration in the industry is shown in Table 1.

It can be seen from Table 1 that the power density of domestic medium frequency induction melting furnaces is basically around 500KW/ton, which is lower than the theoretical optimal value of 600-800KW. This is mainly due to considerations of furnace lining life and production management. Under high power density, electromagnetic stirring will strongly scour the furnace lining, which raises higher requirements for furnace lining materials, furnace building methods, melting processes, materials, auxiliary materials, etc. According to the above configuration, the melting time per heat is 75 minutes (including charging, impurity removal, and temperature conditioning time). If you need to shorten the melting time per heat, you can increase the power density of the power supply by 100KW/ton while keeping the capacity of the furnace body unchanged.
3. Selection of Structure
Generally speaking, the capacity of a medium frequency induction melting furnace can be determined according to the weight of single piece and the required weight of molten iron per working day. Then the power and frequency of the medium frequency power supply are determined. Induction heating equipment is a non-standard product. At present, there is no unified national standard, and the general configuration in the industry is shown in Table 1.

Compared with aluminum shell furnaces, steel shell furnaces have five advantages:
(1) Sturdy, durable, beautiful and elegant. Especially for large-capacity furnace bodies, a rigid structure with higher strength is required. From the perspective of tilting safety, steel shell furnaces are preferred.
(2) The yoke made of silicon steel sheet shields and guides the magnetic lines of force generated by the induction coil, reduces magnetic leakage, improves thermal efficiency, increases output, and saves energy by about 5%-8%.
(3) The furnace cover reduces heat loss and improves the safety of the equipment.
(4) Long service life. Aluminum oxidizes severely at high temperature, resulting in metal toughness fatigue. In foundry workshops, it is common to see aluminum shell furnace shells that have been used for about one year are severely damaged, while steel shell furnaces have less magnetic leakage, and their service life is much longer than that of aluminum shell furnaces.
(5) Steel shell furnaces are far superior to aluminum shell furnaces in safety performance. During melting, aluminum shells are prone to deformation due to high temperature and heavy pressure, resulting in poor safety. Steel shell furnaces use hydraulic tilting mechanism, which is safe and reliable.
4. Why is there a huge price difference for products of the same model and how to choose “medium frequency melting furnace”?
There is a huge price difference for medium frequency induction furnaces of the same model. Take the commonly used 1-ton furnace as an example, the market price sometimes differs by several times. This is related to many factors such as furnace structure, component selection, technical content, after-sales service and quality.
5. Differences in Material Selection
Furnace shell and yoke: For the shell selection of aluminum shell furnaces, the furnace shell of a standard 1-ton aluminum shell furnace is made of 400Kg cast aluminum alloy with a thickness of 40mm, but some manufacturers often produce furnace shells with insufficient weight and thickness. The most important part of a steel shell furnace is the selection of yoke. For steel shell furnaces of the same model, the price varies greatly with different yoke selections. Generally, brand-new grain-oriented Z11 cold-rolled silicon steel sheets with high magnetic permeability should be used. The thickness of the silicon steel sheet is 0.3mm, and a profiling structure is adopted. The inner arc surface is consistent with the outer arc of the induction coil, so that the yoke can fit closely against the outer side of the induction coil and maximize the confinement of the magnetic lines of force diverging outward from the coil. The yoke is clamped by stainless steel plates on both sides, fixed by welding and cooled by water. (Some manufacturers use waste, non-oriented, even silicon steel sheets disassembled from waste transformers to make yokes.)
Copper Tubes and Copper Busbars: The core of a melting furnace is its induction coil. There is a huge gap in performance and price between cold extruded copper tubes and cast copper tubes. T2 cold extruded copper tubes with large cross-section shall be adopted. The surface insulation treatment of copper tubes adopts electrostatic spraying to reach Class H insulation. To ensure insulation strength, wrap the surface once with mica tape and alkali-free glass fiber tape respectively, then apply moisture-proof insulating enamel. Certain gaps shall be reserved between coil turns. When coating refractory mortar inside the coil, let the mortar penetrate into the gaps to enhance its adhesion on the coil. After the refractory mortar is formed, its inner surface is smoothed, which facilitates the removal of furnace lining to protect the coil. Add several turns of stainless steel water cooling rings at the upper and lower ends of the coil to improve overall rigidity and facilitate heat dissipation. (Some manufacturers use cast copper or T3 copper tubes, which have poor conductivity and are prone to cracking and water leakage, so special attention shall be paid)
Thyristors: The quality of thyristors applied by different manufacturers varies greatly. High-quality thyristors feature good temperature sensitivity, fast response and low failure rate. Therefore, thyristors from well-known manufacturers are preferred for reliable and stable quality. (When selecting, you require the electric furnace manufacturer to mark the thyristor's manufacturer and provide the product qualification certificate, etc. Reliable thyristor manufacturers include Xiangfan Taiji Semiconductor Co., Ltd., Xi'an Power Electronics Research Institute, etc.)
Power Cabinet: Regular manufacturers use standard plastic-sprayed panel for cabinet shell, instead of painted iron sheet shell. In addition, the size specifications of the power cabinet are all standard. Substandard manufacturers cut corners on power cabinets, with unqualified height, width and thickness; some even place the reactor outside the power cabinet. Regular manufacturers all install low-voltage switches inside the medium frequency power supply, so users do not need to configure additional voltage switch cabinets. However, some substandard manufacturers do not install low-voltage switches inside the power supply, which invisibly increases users' costs. (High-quality low-voltage switch brands include Huanyu, Chint, Delixi, etc.)
Capacitors: The most important requirement for the capacitor cabinet for reactive power compensation is to be equipped with sufficient capacitors. Generally, the capacitance compensation capacity is 18 to 20 times of the power supply power, that is: Capacitance Compensation Capacity (Kvar) = (20—18) x Power Supply Power. And capacitors from regular manufacturers shall be selected.
Reactors: The main material of a reactor is silicon steel sheet. New products produced by regular manufacturers shall be selected, and recycled second-hand silicon steel sheets shall not be used.
Water Pipe Clamps: There are a large number of water pipe connections in the complete set of medium frequency melting furnace equipment. Strictly speaking, stainless steel clamps shall be used, and a better option is copper unions. Unions are easy to install and disassemble, and require no maintenance. They are especially suitable for water-cooled cables, which is conducive to current transmission, will not cause water leakage, and is safe and reliable.
Besides the points above, the selection of other components is also very important, such as inverter non-inductive capacitors, non-inductive resistors, water-cooled cables, connecting copper busbars, water pipes, etc. All these will affect the quality and price of the equipment, so we will not elaborate on them here. We hope you can pay attention when selecting and purchasing, try to require the melting furnace manufacturer to provide the list of main components and their manufacturers, and not only compare prices blindly while ignoring the internal structure and quality of the equipment.