The main causes for the failure or difficulty in starting the inverter circuit of a medium frequency power supply are as follows.
(1) Inter-turn short circuit of the induction coil. If the induction coil has poor cooling performance for a long time, its insulation will be damaged, resulting in inter-turn short circuit. Conductive contaminants such as dust and oxide scale on the induction coil can also cause this problem. Arcing occurs when starting the medium frequency power supply, and frequent arcing will lead to breakdown of the induction coil. To address this issue, clean the impurities on the surface of the induction coil, then brush insulating varnish or pad an asbestos sheet.
(2) Short circuit between the induction coil and the shell of the electric arc furnace. Causes include loose induction coil, excessive dust accumulation inside the furnace, and discharge of the induction coil through the furnace base. To solve this, reinforce the induction coil and clean up the dust.
(3) Short circuit of the copper busbar connecting the medium frequency output end and the induction coil. Foreign matters or loosely fixed copper busbars can cause short circuit between the busbars.
(4) Short circuit of the capacitor shell to the ground. In this case, check for water leakage, whether there is excessive dust accumulation on the capacitor base, and whether the ceramic base of the capacitor is missing.
(5) Open circuit of the water-cooled cable, or burnout of the copper busbar that outputs power to the load.
(6) Check whether the insulation of the current transformer is damaged; remove the current transformer to check its insulation condition; use a multimeter to measure whether the coil is burned out, and check whether the wiring sequence is correct. If all inspections above are normal, further check whether the output value of the potentiometer for adjusting current signal is too small, and readjust the amplitude of the output current signal.
(7) Check whether the inversion angle of the inverter circuit is too small. If it is too small, adjust the inversion angle; if it is normal, check whether the current polarity is reversed. If the polarity is not reversed, check whether the inverter thyristor has trigger pulse. If everything works properly, check whether the inverter thyristor is damaged. If it is damaged, replace it with a thyristor of the same model and specification.