What are the causes of capacitor breakdown?

📅 2020-08-08 08:52:07 ✍️ Author:admin 👁️ 572 views
Ready
1.6x

The compensation capacitors of intermediate frequency power supply are generally installed in groups on the capacitor rack. During inspection, you should first determine the group where the broken-down compensation capacitor is located. Disconnect the connection points between the busbar of each group of compensation capacitors and the main busbar, and measure the resistance between the two busbars of each group of compensation capacitors. Under normal conditions, the resistance should be infinite.

 

The insulation resistance of intermediate frequency power supply compensation capacitors includes insulation resistance between two poles, between multiple poles, and insulation resistance from two poles to the shell. Since a compensation capacitor is composed of series and parallel capacitor components, insulation deterioration of individual components will not reduce the insulation resistance of the entire compensation capacitor, so it is difficult to detect defects by testing inter-electrode insulation resistance. Therefore, inter-electrode insulation resistance testing is generally not performed, and only insulation resistance testing of two poles or multiple poles to the shell is carried out.

Megohmmeters of different voltage levels shall be selected according to different rated voltages of compensation capacitors. Take a 750V rated voltage as an example, a 1000V megohmmeter is used. Discharge the compensation capacitor first before testing. During testing, shake the megohmmeter to the specified speed until its pointer stabilizes, then connect the megohmmeter to the two poles of the compensation capacitor and continue rotating the megohmmeter. At the beginning, as the compensation capacitor is being charged, the pointer will drop and the resistance will return to zero. Continue rotating the megohmmeter, then the reading will rise slowly until it stabilizes. The reading at this time is the inter-electrode resistance of the compensation capacitor. Under normal circumstances, the resistance for 1000V test shall not be lower than 1MΩ. After reading the result, remove the megohmmeter leads first, then stop shaking. Otherwise, the meter head is easily burned when the compensation capacitor discharges. After testing, discharge the compensation capacitor to avoid electric shock.

After confirming the faulty compensation capacitor group, disconnect the soft copper tape leading from each compensation capacitor to the busbar, inspect them one by one to find the broken-down compensation capacitor  Each compensation capacitor is composed of 4 cores, the shell is one pole, and the other pole is led to the end cover through 4 insulators respectively. Generally only one core will be broken down. After disconnecting the lead on this insulator, this compensation capacitor can continue to be used, and its capacity is 3/4 of the original. Another fault of the compensation capacitor isleakage, which generally does not affect use, but fire prevention should be noted.

The angle steel for installing compensation capacitors is insulated from the compensation capacitor rack. If insulation breakdown occurs, the main circuit will be grounded. Measuring the resistance between the compensation capacitor shell lead and the compensation capacitor rack can judge the insulation status of this part. The main reasons for breakdown of compensation capacitors are as follows.

(1) Cathode grounding. During the normal operation of the intermediate frequency power supply, if the compensation capacitor has poor insulation, cathode grounding of the compensation capacitor will occur and cause breakdown of the compensation capacitor shell. If this situation occurs, it is necessary to conduct insulation testing on the compensation capacitor. If it is broken down, the compensation capacitor with the same model, specification and capacity shall be replaced.

(2) Poor cooling. During long-term use of the intermediate frequency power supply, scale may form in the cooling water pipe of the compensation capacitor, or debris may enter and block the cooling water pipe, resulting in overheating and damage of the compensation capacitor. Therefore, you should pay attention to observing the flow of cooling water for the compensation capacitor during use, and take corresponding measures if the flow is abnormal.

(3) Excessive intermediate frequency voltage. During long-term use of the intermediate frequency power supply, if the intermediate frequency voltage is adjusted too high, higher than the rated voltage of the compensation capacitor (common rated voltage specifications of capacitors include 750V, 1200V, etc.), it will cause compensation capaci

tor to break down due to overvoltage. If this situation occurs, you need to lower the intermediate frequency voltage or replace the compensation capacitor with a model with a higher voltage resistance level.

(4) Short circuit of compensation capacitor. In a parallel inverter, the compensation capacitor is connected in parallel with the induction coil. When the compensation capacitor is short-circuited, it will cause a short circuit in the load loop, which prevents the load loop from generating oscillation and makes the medium frequency power supply unable to work. To find the short-circuited compensation capacitor, the elimination method can be used: disconnect two or three compensation capacitors each time and test the startup. If the medium frequency power supply can start normally, it means that there is a breakdown short circuit in the disconnected group of compensation capacitors. Then you can use the R×10k gear of a multimeter to measure both ends of the compensation capacitor. The resistance of a short-circuited compensation capacitor is zero and it cannot be charged with voltage; for a normal compensation capacitor, the reading is zero when the multimeter is just connected, and then the pointer gradually moves to the high resistance end. Generally, compensation capacitors with resistance above 500kΩ are normal.

(5) Withstanding voltage reduction of compensation capacitor. At present, the main models of compensation capacitors used in medium frequency power supplies are RWF0. 75- 180-1 or RWF0.75-360-1, etc., and their rated withstanding voltage is 750V.When the withstanding voltage of the compensation capacitor drops, inversion failure will occur after the medium frequency power supply works at a certain fixed medium frequency voltage.

Open circuit of compensation capacitor. When the compensation capacitor is open-circuited, it has little impact on the normal operation of the medium frequency power supply, only the working frequency of the power supply is higher than the normal value. At this time, you only need to connect several new compensation capacitors in parallel to the tank circuit to bring the frequency back to the normal value.

(7) Loose connecting bolts between compensation capacitor and output busbar, between busbars, and between busbar and water-cooled cable. Since the current flowing through the busbar is very large, the temperature of the busbar is also high during operation, so it is easy to cause connecting bolts to loosen. After loosening, the contact resistance increases, which further raises the temperature of the connection. Excessive temperature caused by loosening will oxidize the surface of the busbar connection, leading to poor contact and arcing. Arcing interference often causes inversion failure. Therefore, all connecting bolts on the busbar of the medium frequency power supply should be checked and tightened regularly to avoid poor contact and open circuit faults.

(8) Short circuit to ground of induction coils and capacitors, same as short circuit to ground of the main circuit, often causes the serious fault of burning thyristors. Therefore, when the thyristor burning fault occurs, in addition to focusing on checking the protection system, you should also check whether there is short circuit or poor insulation between the induction coil and ground, or between the compensation capacitor casing and ground. Generally, use the R×1k gear of a multimeter to check the resistance to ground of the induction coil and the compensation capacitor casing, which should be around 10kΩ. The newly built furnace lining has low insulation resistance due to moisture, but it should not be less than 5kΩ. For insulation degradation, you can use a 500~2500V megohmmeter for inspection.